Analisis Kinerja Lightning Arrester Berdasarkan Arus Bocor pada Gardu Induk Kualanamu 150 kV PT.PLN P3B Sumatera
Performance Analysis of Lightning Protection Based on Leakage Current at the Kualanamu 150 kV Substation PT.PLN P3B Sumatra
Abstract
PT.PLN (Persero) P3B SUMATERA Kualanamu Substation. Lightning arresters function
to channel excess voltage so as not to interfere with and damage equipment. This study
was conducted because there has been no research on lightning arresters that are more
than 10 years old at the Kualanamu Substation.
The method used in this study is a quantitative method. The variables needed are leakage
current data at the Kualanamu Substation in 2022-2023. The research procedure is a
literature study, collection of leakage current data, analysis of arrester performance,
analyzing test results, follow-up. lightning arrester performance is based on leakage
current measured using the Leakage Current Monitor by comparing it with the standards
determined by PLN. While the age limit of the lightning arrester is calculated using a
linear regression equation.
Based on the analysis carried out, 100% of the arrester performance at the Kualanamu
substation is in good condition and is suitable for operation because it is still below the
standard