| dc.contributor.advisor | Hardi, Surya | |
| dc.contributor.advisor | Sinulingga, Emerson Pascawira | |
| dc.contributor.author | Wardani, Dwi Putri | |
| dc.date.accessioned | 2025-10-27T01:53:50Z | |
| dc.date.available | 2025-10-27T01:53:50Z | |
| dc.date.issued | 2025 | |
| dc.identifier.uri | https://repositori.usu.ac.id/handle/123456789/110493 | |
| dc.description.abstract | Substations are essential components in electrical transmission systems
and are highly susceptible to disturbances, particularly from lightning strikes
both direct and indirect. To safeguard equipment and ensure operational safety, a
protection system is necessary. One such method is the grounding system, which
should ideally exhibit low soil resistivity. The accuracy of soil resistivity
measurements is influenced by the type of soil and the design of the grounding
grid configuration. This study investigates grounding systems with and without
square-shaped ground rods, including an assessment of touch and step voltages
on two-layer soil, as well as arrester modeling in accordance with IEEE
standards. Overvoltage simulations caused by lightning strikes were conducted
using ATP-Draw software, incorporating various grid configurations based on
conductor spacing and length. The calculation results yielded K coefficient values
both below and above zero, but still within the safety limits defined by substation
design standards. Additionally, the simulation demonstrated that lightning
arresters effectively protect the transmission system, achieving a protection factor
(PF) of 22.15%. | en_US |
| dc.language.iso | id | en_US |
| dc.publisher | Universitas Sumatera Utara | en_US |
| dc.subject | Substations | en_US |
| dc.subject | Grid Configuration | en_US |
| dc.subject | Lightning Surge | en_US |
| dc.subject | overvoltages | en_US |
| dc.subject | arresters | en_US |
| dc.subject | ATP-Draw software | en_US |
| dc.title | Analisis Keamanan Pentanahan Grid dan Proteksi Gardu Induk dengan Variasi Arus Surja Petir Menggunakan Software ATP-Draw | en_US |
| dc.title.alternative | Grid Grounding Safety Analysis and Substation Protection With Lightning Surge Current Variations Using ATP-Draw Software | en_US |
| dc.type | Thesis | en_US |
| dc.identifier.nim | NIM217034007 | |
| dc.identifier.nidn | NIDN0007065905 | |
| dc.identifier.nidn | NIDN0030037707 | |
| dc.identifier.kodeprodi | KODEPRODI20101#Teknik Elektro | |
| dc.description.pages | 96 Pages | en_US |
| dc.description.type | Tesis Magister | en_US |
| dc.subject.sdgs | SDGs 4. Quality Education | en_US |