Uji Eksperimental Pengaruh Jarak Baffle terhadap Unjuk Keria Termal dan Penurunan Tekanan pada Alat Penukar Kalor Shell and Tube I-2 Pass Susunan Tabung Segi Tiga
View/ Open
Date
2007Author
Kamil, Idham
Advisor(s)
Napitupulu, Farel Hasiholan
Zamanhuri
Sitorus, Tulus Burhanuddin
Metadata
Show full item recordAbstract
An experimental and theoretical iwestigation wos made to find out the effect of the
ffictiveness atid pressure drop oti the 1-2 pass shell and rube hem aichaiigar with
different bafrle distance for staggered tube arrdngement. A heat exchanger using
segmental bafrle wtth 23,85% baffle cut is tested with dffirent baffle distance which
are: 36 mm, 40 mm, 45 mm, 45 mm, 5l mm, 59 mm, and 7l mm. The experimental
results showed that a mmimum coeficient heat transfer with Nusselt number (Nu)
and minimum pressure drop with friction factor fi is found in 45 mm of bafrle
distance. It is alsofound tlat the empirical correlation between Nusselt number (Nu)-
andfrictionfactoi (fl is governed iy Nu:0,1015 Re0'63e3 and f :4,1728 Re'0'281e8
.&/D)0'"337o, , 98;46,33 < Re < 37645,5A andfor 0,27 SL/D.50,54